Region AMERICA

    Standby Power

    STANDBY DIESEL

    STANDBY DIESEL

    Find your generator set
    Version

    Model

    HFSG-60 T6U

    Three phase | Diesel |

    Model

    Powered by FPT_IVECO

    Alternator STAMFORD

    Emissions TIER III

    PRP
    ESP
    COP
    Power kVA
    75
    Power kW
    60
    Voltage Frequency Phase Alternator Connection type Generator set data sheet
    120/208 V 60 Hz Three phase UCI224F Star - Parallel Download
    120D/240 V 60 Hz Three phase UCI224F Delta-series Download
    138/240 V 60 Hz Three phase UCI224E Star - Parallel Download
    277/480 V 60 Hz Three phase UCI224E Star-series Download
    347/600 V 60 Hz Three phase UCI224E Star-series Download
    • Engine Specifications 1,800 r.p.m.
    • Rated Engine Output: 61kW prp ; 67kW standby
    • Manufacturer: FPT_IVECO
    • Model: NEF45SM2X
    • Engine Type: 4-stroke diesel
    • Injection Type: Direct
    • Aspiration Type: Turbocharged
    • Number of cylinders and arrangement: 4-L
    • Bore and Stroke: 4.09 x 5.2 in
    • Displacement: 274.59 CID
    • Cooling System: Liquid (water + 50% glycol)
    • Lube Oil Specifications: ACEA E3 - E5
    • Compression Ratio: 17.5:1
    • Fuel Consumption ESP: 5.05 Gal/h
    • Fuel Consumption 100% PRP: 4.57 Gal/h
    • Fuel Consumption 80 % PRP: 3.8 Gal/h
    • Fuel Consumption 50 % PRP: 2.72 Gal/h
    • Lube oil consumption with full load: 0.1 % of fuel consumption
    • Total oil capacity including tubes, filters 3.38 Gal
    • Total coolant capacity: 4.89 Gal
    • Governor Type Mechanical
    • Air Filter Type Dry
    • EPA TIER 3
    • 12V electrical system
    • Dry air filter

    • Generator: STAMFORD
    • Model: UCI224F
    • Poles: 4
    • Connection type (standard): Star - Parallel
    • Mounting type: S-3 11"1/2
    • Insulation: H class
    • Enclosure (according IEC-34-5): IP23
    • Exciter system: Self-excited, brushless
    • Voltage regulator: A.V.R. (Electronic)
    • Bracket type: Single bearing
    • Coupling system: Flexible disc
    • Coating type: Standard (Vacuum impregnation)

    • Generator: STAMFORD
    • Model: UCI224E
    • Poles: 4
    • Connection type (standard): Star - Parallel
    • Mounting type: S-3 11"1/2
    • Insulation: H class
    • Enclosure (according IEC-34-5): IP23
    • Exciter system: Self-excited, brushless
    • Voltage regulator: A.V.R. (Electronic)
    • Bracket type: Single bearing
    • Coupling system: Flexible disc
    • Coating type: Standard (Vacuum impregnation)

    • Generator: STAMFORD
    • Model: UCI224E
    • Poles: 4
    • Connection type (standard): Star-series
    • Mounting type: S-3 11"1/2
    • Insulation: H class
    • Enclosure (according IEC-34-5): IP23
    • Exciter system: Self-excited, brushless
    • Voltage regulator: A.V.R. (Electronic)
    • Bracket type: Single bearing
    • Coupling system: Flexible disc
    • Coating type: Standard (Vacuum impregnation)

    • Generator: STAMFORD
    • Model: UCI224E
    • Poles: 4
    • Connection type (standard): Star-series
    • Mounting type: S-3 11"1/2
    • Insulation: H class
    • Enclosure (according IEC-34-5): IP23
    • Exciter system: Self-excited, brushless
    • Voltage regulator: A.V.R. (Electronic)
    • Bracket type: Single bearing
    • Coupling system: Flexible disc
    • Coating type: Standard (Vacuum impregnation)

    • Generator: STAMFORD
    • Model: UCI224F
    • Poles: 4
    • Connection type (standard): Delta-series
    • Mounting type: S-3 11"1/2
    • Insulation: H class
    • Enclosure (according IEC-34-5): IP23
    • Exciter system: Self-excited, brushless
    • Voltage regulator: A.V.R. (Electronic)
    • Bracket type: Single bearing
    • Coupling system: Flexible disc
    • Coating type: Standard (Vacuum impregnation)
    • - SOUNDPROOFED VERSION.
    • Tilting cap in the exhaust
    • Bodywork made from high quality steel plate
    • Full access for maintenance (water, oil and filters, no need to remove the canopy)
    • Slide carriage and brackets for transportation with forklift (Optional)
    • Fuel tank (Optional)
    • - ELECTRICAL SYSTEM.
    • Main line ABB UL listed circuit breaker for overload protection
    • 6 Amp Battery charger, 12V DC, UL Listed (Optional)
    • Battery Blanket (Optional)
    • Water Jacket Heater (Optional)
    • - EXHAUST SYSTEM.
    • Maximum exhaust temperature: 932 ºF
    • Maximum allowed back pressure: 20.05 inH2O
    • Heat dissipated by exhaust pipe: 778 KCal/Kwh
    • - NECESSARY AMOUNT OF AIR.
    • Intake air flow: 247 scfm
    • Cooling Air Flow: 4,873 scfm
    • Alternator fan air flow: 595 scfm
    • - STARTING SYSTEM.
    • Starting power: 3 kW
    • Starting power: 4.02 HP
    • Recommended battery: 100 Ah
    • Auxiliary Voltage: 12 Vdc
    • - FUEL SYSTEM
    • Fuel Oil Specifications: Diesel
    • Other fuel tank capacities: 110 Gal
    • - DIMENSIONS.
    • Length: 100 in
    • Height: 47 in
    • Width: 36.02 in
    • Maximum shipping volume: 97.82 ft3
    • Weight with liquids in radiator and sump: 2,635 Lbs
    • Sound pressure level: 73 ± 2.4 dB(A)@7m

    Dimensions

    Dimensions
    Length254100.00
    Width91.536.02
    Height119.447.01

    Autonomy

     
     

    29 h

    Weight

    Weight

    Weight with fluids in radiator and crankcase

    1,195.22

    2,635.45

    Dimensions

    Dimensions
    Length254100.00
    Width91.536.02
    Height157.562.01

    Autonomy

     
     

    29 h

    Fuel capacity

    416.40

    109.93

     

    Necessary

    Technical cookies are strictly necessary for our website to function and to be able to navigate through it. These types of cookies are those that, for example, allow us to identify you, give you access to certain restricted parts of the page if necessary, or remember different options or services already selected by you, such as your privacy preferences. Therefore, they are activated by default, your authorization is not required in this regard.

    Statistics

    The analysis cookies allow us to study the navigation of the users of our website in general (for example, which sections of the page are the most visited, which services are used the most and if they work correctly, etc.). Based on the statistical information on navigation on our website, we can improve both the operation of the page itself and the different services it offers. Therefore, these cookies do not have an advertising purpose, but only serve to make our website work better, adapting to our users in general. By activating them you will contribute to this continuous improvement.