Region AMERICA

    Standby Power

    STANDBY DIESEL

    STANDBY DIESEL

    Find your generator set
    Version

    Model

    HYSG-40 M6U

    Single phase | Diesel |

    Model

    Powered by YANMAR

    Alternator STAMFORD

    Emissions TIER IV

    PRP
    ESP
    COP
    Power kVA
    40
    Power kW
    40
    Voltage Frequency Phase Alternator Connection type Generator set data sheet
    120/240 V 60 Hz Single phase S1L2.N1 Series Download
    • Engine Specifications 1,800 r.p.m.
    • Rated Engine Output: 45.4kW prp ; 50.2kW standby
    • Manufacturer: YANMAR
    • Model: 4TNV98T ZGGEH
    • Engine Type: 4-stroke diesel
    • Injection Type: Direct
    • Aspiration Type: Turbocharged
    • Number of cylinders and arrangement: 4-L
    • Bore and Stroke: 3.86 x 4.33 in
    • Displacement: 202.53 CID
    • Cooling System: Coolant
    • Lube Oil Specifications: SAE 3 class 10W30 / API grade CD,CF
    • Compression Ratio: 18.1:1
    • Fuel Consumption ESP: 3.29 Gal/h
    • Fuel Consumption 100% PRP: 2.98 Gal/h
    • Fuel Consumption 75 % PRP: 2.27 Gal/h
    • Fuel Consumption 50 % PRP: 1.61 Gal/h
    • Lube oil consumption with full load: 0.27
    • Total oil capacity: 2.69 Gal
    • Total coolant capacity: 2.38 Gal
    • Governor Type Electrical
    • Air Filter Type Dry
    • Inner diameter exhaust pipe: 45 in
    • EPA TIER 4 INT.
    • 12V electrical system
    • Dry air filter
    • Generator: STAMFORD
    • Model: S1L2.N1
    • Poles: 4
    • Connection type (standard): Series
    • Mounting type: S-3 11"1/2
    • Insulation: H class
    • Enclosure (according IEC-34-5): IP23
    • Exciter system: Self-excited, brushless
    • Voltage regulator: A.V.R. (Electronic)
    • Bracket type: Single bearing
    • Coupling system: Flexible disc
    • Coating type: Standard (Vacuum impregnation)
    • - SOUNDPROOFED VERSION.
    • Oversized chassis to protect the bodywork
    • Tilting cap in the exhaust
    • External emergency stop switch
    • Bodywork made from high quality steel plate
    • Full access for maintenance (water, oil and filters, no need to remove the canopy)
    • Slide carriage and brackets for transportation with forklift (Optional)
    • Fuel tank (Optional)
    • - ELECTRICAL SYSTEM.
    • Main line ABB UL listed circuit breaker for overload protection
    • 6 Amp Battery charger, 12V DC, UL Listed (Optional)
    • Battery Blanket (Optional)
    • Water Jacket Heater (Optional)
    • - EXHAUST SYSTEM.
    • Maximum exhaust temperature: 887 ºF
    • Exhaust Gas Flow: 26,613.00 cfs
    • Maximum allowed back pressure: 39.00 inH2O
    • - NECESSARY AMOUNT OF AIR.
    • Intake air flow: 137 scfm
    • Cooling Air Flow: 2,492 scfm
    • Alternator fan air flow: 449 scfm
    • - STARTING SYSTEM.
    • Starting power: 2.3 kW
    • Starting power: 3.09 HP
    • Recommended battery: 92 Ah
    • Auxiliary Voltage: 12 Vdc
    • - FUEL SYSTEM
    • Fuel Oil Specifications: Diesel
    • Maximum power suction pump: 30 mm Hg
    • Maximum return feed pump: 250 mm Hg
    • Other fuel tank capacities: 89 Gal
    • - DIMENSIONS.
    • Length: 87.99 in
    • Height: 45 in
    • Width: 36.02 in
    • Maximum shipping volume: 82.64 ft3
    • Weight with liquids in radiator and sump: 2,172 Lbs
    • Sound pressure level: 69 ± 2.4 dB(A)@7m

    Dimensions

    Dimensions
    Length223.587.99
    Width91.536.02
    Height114.345.00

    Autonomy

     
     

    39 h

    Weight

    Weight

    Weight with fluids in radiator and crankcase

    985.20

    2,172.37

    Dimensions

    Dimensions
    Length223.587.99
    Width91.536.02
    Height147.357.99

    Autonomy

     
     

    39 h

    Fuel capacity

    336.90

    88.94

     

    Necessary

    Technical cookies are strictly necessary for our website to function and to be able to navigate through it. These types of cookies are those that, for example, allow us to identify you, give you access to certain restricted parts of the page if necessary, or remember different options or services already selected by you, such as your privacy preferences. Therefore, they are activated by default, your authorization is not required in this regard.

    Statistics

    The analysis cookies allow us to study the navigation of the users of our website in general (for example, which sections of the page are the most visited, which services are used the most and if they work correctly, etc.). Based on the statistical information on navigation on our website, we can improve both the operation of the page itself and the different services it offers. Therefore, these cookies do not have an advertising purpose, but only serve to make our website work better, adapting to our users in general. By activating them you will contribute to this continuous improvement.

    Marketing

    Marketing cookies are used to track visitors on web pages. The intention is to show ads relevant and attractive to the individual user, and therefore more valuable to publishers and third-party advertisers.